tML® - TP Trunk Cables Telco F/F

tML® - TP Trunk Cable Telco F/F 180° shielded 1000BaseT PUR length: xx meters

P/N: TML-TELCO-FF-xx

Description

The tML® – TP trunk cable is intended for the connection of two tML®- TP Modules.

Technical data

tML® - TP Trunk Cable is preterminated on both ends with a Telco 50pos. female connector. The cable is very slim and flexible. Each cable is marked with sequential serial number and article number.

Cable S/FTP Round Cable 24x2xAWG 27/7, Pet-Al foil around each pair, 3 layers of screened pairs (2+8+14), PUR
Outer Diameter 14.5 mm
Weight 158 kg/km
bending radius without load 8xD mm
bending radius with load 4xD mm
Connectors 2 x Telco 50pos. Female 180° shielded with screws 
Tests Link Performance Tests, Elektronischer Test on short-circuit and Visual Final Inspection; all measured values are electronically archived
  QS-Managementsystem nach ISO 9001, ISO 14001 und TL 9000

xx - stands for the cable length in meters (max. length is 60m)

  • Cable construction
    Leader Cu-strands, blank Ø 0.42 mm
    Isolation Form-Skin polyethylene, Ø 0.98 mm
    Standing 2 wires to the pair
    Pair shielding aluminium- coated plastic compound foil
    Stranding to the soul 24 Pair (PiMF) to the soul in Layering (2+8+14)
    Overall shielding wrapping double aluminium- coated plastic compound foil
      Drain wire AWG26 tinned
      Cu-braid 24x8x0.18 mm tinned (about 77 % coverage)
    Protective sheath PUR
      Wall thickness 1.3 mm
    Technical offer date
    Colour black
    Outside diameter 15.2 mm
    Fire load 2383 MJ/km
      0.606 kWh/m
    Weight 237 kg/km
    Cu-number 140
    Traction 600 N
    Mechanical properties
    Bending radii ≥ 75 mm without tensile load
      ≥ 150 mm with tensile load
    Poerating temperature range resting -20 °C to +60°C
      moved 0 °C to +50°C
    electrical properties (for 20°C ± 5°C)
    Loop resistance ≤ 340 Ω/km
    Unbalance resistor ≤ 3 %
    Insulation resistance (500 V) ≥ 2000 MΩ x km
    Capacity for 800 Hz nom. 43 nF/km
    Unbalance capacity (pair/earth) ≤ 1500 pF/km
    Impedance (1-100 MHz) (100 ± 15) Ω
    Relative propagation speed about 79 %
    Signal propagation delay ≤ 427 ns/100 m
    Runtime difference ≤ 12 ns/100 m
    Test voltage (DB) Core/core and core/screen 1000 V
    Coupling resistance for 1 MHz ≤ 10 mΩ/m
      for 10 MHz ≤ 10 mΩ/m
      for 30 MHz ≤ 30 mΩ/m
      for 100 MHz ≤ 60 mΩ/m
    Transmission properties acc. category 5e (for 20°C)
    f


    (MHz)
    Damping


    (dB/10m)
    nom.
    NEXT


    (dB)
    min. / nom.
    PS-NEXT


    (dB)
    min. / nom.
    ELFEXT


    (dB/10m)
    min. / nom.
    PS-ELFEXT


    (dB/10m)
    min. / nom.
    Return
    loss

    (dB)
    min.
    1 0.3 65 / 71 62 / 68 64 / 68 61 / 65 23
    4 0.6 56 / 62 53 / 59 52 / 56 49 / 53 24
    10 1.0 50 / 56 47 / 53 44 / 48 41 / 45 25
    16 1.3 47 / 53 44 / 50 40 / 44 37 / 41 25
    20 1.4 46 / 51 43 / 48 38 / 42 35 / 39 25
    31.2 1.8 43 / 49 40 / 46 34 / 38 31 / 35 25
    62.5 2.6 38 / 44 35 / 41 28 / 32 25 / 29 23
    100 3.2 35 / 41 32 / 38 24 / 28 21 / 25 21
    125 3.6   - / 40   - / 37   - / 26   - / 23  
P/N Description Quantity
TML-TELCO-FF-xx tML® - TP Trunk Cable Telco F/F 180° shielded 1000BaseT PUR length: xx meters

back

Datasheet

Announcement texts

Media objects

tML - Flyer EN 24.03.2016

tML24 Flyer EN 12.09.2019