TP Trunk Cables

tBL® - TP Trunk Cable both ends RJ45 DC 6fold Module (one enclosed) Cat.6A UC Future 24x2xAWG23 LSHF

P/N: T-T6D/T6D-N23CxxxxU

Technical data

xxxx Length in cm
  • System platforms tML®/ tSML
     
    4x tBL® - 6fold Modules can be integrated in a tSML - TP Module.
     
    1x tBL® - 6fold Module can be integrated in a tML® - TP Module.
    Equipping
    6x tBL® RJ45 DC Module Cat.6A
  • Construction plastic with insulation displacement connection
    Gold plating termination block 30 µ"
    Color transparent yellow
    Application Installation cable with solid wire, AWG 22 to AWG 24 and flex.
      Plug bears small flag-like installation guide with color codes for pin-out according to EIA/TIA 568 A and B.
  • Construction
    Type UC FUTURE COMPACT AWG23/1 Cat.7 S/FTP 24P
    Conductor Bare copper wire, diamter 0.56 mm (AWG23)
    Insulation Foam-skin PP, diameter 1.4 mm
    Twisting 2 insulated wires to the pair
    Pair screening Pet-Al foil around each pair
    Stranding 3 layers of screened pairs (2+8+14)
    Screen Tinned copper braid 85% coverage
    Sheath LSHF

    Application
    IEEE 802.3: 10Base-T; 100Base-T; 10GBase-T, ISDN; xDSL
    IEEE 802.5 16 MB; ISDN; TPDDI; ATM155Mbit/s
    The conductor diameter is smaller compared to the standard installation cables. This leads to an increased attenuation and therefore the operating distance is reduced (80 m instead of 90 m installation cable in standard permanent link).

    Standards
    IEC 61156-6 work area cable
    ISO/IEC 11801
    EN 50173-5;EN 50288-4-2
    IEEE 802.3af

    Flame resistance
    IEC 60332-1
    LSHF-FR IEC 60332-3-24; IEC 60754-2; IEC 61034; EN 50399 Class Dca

    Mechanical properties
    Minimum bending radius Without load ≥ 100 mm
      With load ≥ 200 mm
    Temperature range  During operation -20°C up to +60°C
      During installation 10°C up to +40°C
    Electrical properties at 20°C ± 5°C
    Loop resistance   ≤ 176 Ω/km
    Resistance unbalance   ≤ 2%
    Test voltage core/core 1000 VDC 1 min
      core/screen 1000 VDC 1 min
    Capacitance 800 Hz Nom. 43 nF/km
    Capacitance unbalance   ≤ 1500 pF/km
    Impedance 1-100 MHz 100 Ω ± 5 Ω
    Nominal velocity of propagation   ca. 79%
    Propagation delay Nominal < 450 ns/100m
    Delay skew Nominal < 15 ns/100m
    Insulation resistance 500 V ≥ 2000 MΩkm
    Transfer impedance bei 1 MHz ≤ 5 mΩ /m
      bei 10 MHz ≤ 5 mΩ /m
      bei 30 MHz ≤ 10 mΩ /m
    Coupling attenuation   ≥ 85 dB
    Electrical Data (nominal) acc. to Cat.7 (at 20°C)
    F in


    MHZ
    Atten-
    uation

    dB/90m
    NEXT


    dB
    PS-
    NEXT

    dB
    ACR


    dB/100m
    PS-ACR


    dB/100m
    ELFEXT


    dB/100m
    PS-
    ELFEXT

    dB/100m
    Return
    loss

    dB
    1.0 1.8 100 97 98 95 105 105 -
    4.0 3.4 100 97 97 94 105 102 27
    10.0 5.4 100 97 95 92 97 94 30
    16.0 6.8 100 97 93 90 93 90 30
    20.0 7.7 100 97 92 89 91 88 30
    31.2 9.6 100 97 90 87 87 84 30
    62.5 13.7 100 97 86 83 81 78 30
    100.0 17.4 100 97 83 80 77 74 30
    125.0 19.5 95 92 75 72 75 72 26
    155.5 21.9 94 91 72 69 73 70 26
    175.0 23.3 93 90 70 67 72 69 25
    200.0 25.0 92 89 67 64 71 68 25
    250.0 28.1 90 87 62 59 69 66 24
    300.0 30.9 89 86 58 55 67 64 24
    400.0 38.3 87 84 48 45 64 61 23
    500.0 43.0 86 83 43 40 61 58 22
    600.0 44.8 85 82 40 37 60 57 22
    Technical Data
    Designation J-09YS(ST)CH
    Outer diameter 18 mm
    Fire load 3120 MJ/km
    Fire load 0.87 kWh/m
    Reaction to Fire Dca-s2, d2, a1
    Weight 330 kg/km
    Copper content 165 kg/km
    Tensile force 840 N
  • Mechanical properties
    Type RJ45 Jack shielded
    Connector standard IEC 60603-7-5-1
    Installation dimension 19.3 x 14.7 mm
    Mating force ≤30 N
    Mating cycles (RJ45 side) ≥750
    Mating cycles (opposite side) ≥100
    Housing material nickel-plated die-cast zinc
    Insulation components material PC aqua
    Gold plating in contact area 30 µ"
    Contacting AWG 27-22
    Cable diameter 5-10 mm
    Environmental requirements
    Connection class IP20
    Temperature range -40°C to +70°C
    Electrical properties
    Contact resistance ≤20 mΩ

    Insulation resistance between contacts

    ≥500 MΩ

    Dielectric withstanding voltage contact – contact

    ≥1000 V DC/AC

    Dielectric withstanding voltage contact – screen

    ≥1500 V DC/AC

    Current-carrying capacity at 50°C

    1.25 A

    PoE+ per IEEE 802.3at

    PoE+
    Transmission characteristics
    10 GbE supported
    Cat.6A ISO/IEC 11801 AM1 and AMD2, Link length: >1 m
P/N Description Quantity
T-T6D/T6D-N23Cxxxx tBL® - TP Trunk Cable both ends RJ45 DC 6fold Module Cat.6A UC Future 24x2xAWG23 LSHF
T-T6D/T6D-N23CxxxxU tBL® - TP Trunk Cable both ends RJ45 DC 6fold Module (one enclosed) Cat.6A UC Future 24x2xAWG23 LSHF
T-TKT/TKT-N23Cxxxx tBL® - TP Trunk Cable both ends preterminated 6x termination block Cat.6A UC Future 24x2xAWG23 LSHF

back

Datasheet

Announcement texts

Media objects

tBL® - RJ45 Module Cat.6A Certificate

CPR/BauPVO

TA COMPACT 23 C7 S/FTP 24P LSHF-FR (ZMTA-100002)