FO Trunk Cables Premium

FO Universal Cable 12x E2000/12x E2000 12E9/125µ OS2 LSHF, Length: xxxx

P/N: P-E2/E2-09B12Exxxx

  • Type E2000 UPC
    Ferrule Ceramic
    Ferrule Hole 125.5 µ
    Ferrule Concentricity ≤ 0.6 µ
    Connector colour Blue
    Lever Colour Blue
    Boot colour Blue
    Manufacturer RDM
    Optical performance
    FiberTypeWavelengthInsertion loss typ.Insertion loss max.Return loss min.
    9/125µ E2000 UPC 1550 nm ≤ 0.10 dB 0.25 dB 55 dB
  • Fan-out length 50 mm
    Ø Fan-out 16 mm
    Ø Single unit 1.7 - 2 mm
    Single unit length 78 ± 5 cm (not stepped)
  • Mechanical characteristics
    Temperature range Storage -25 to +70°C, IEC 60794-1-22 F1
      Pulling in -10 to +50°C
      Operation -25 to +60°C
    Tensile performance IEC 60794-1-21 E1
    Crush resistance IEC 60794-1-21 E3
    Impact IEC 60794-1-21 E4
    Repeated bending IEC 60794-1-21 E6
    Torsion IEC 60794-1-21 E7
    Bend IEC 60794-1-21 E11
    Water penetration IEC 60794-1-22 F5
    General characteristics

    Sheath colour

    green, similar to RAL 6016

    Zero halogen, non corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
    Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
    Flame spread IEC 60332-3-24, EN 50266-2-4, VDE 0482-266-2-4
    Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
    Reaction to fire (Euroclasses) EN 13501-6: Dca-s2,d1,a1
    Cabletype Universal U-DQ(ZN)BH for indoor and outdoor use
     

    non metallic, dry interstices, rodent protection, flame retardant, in accordance with IEC 60332.1and IEC 60332.3 C

    Fibertype E9/125 G.652.D
    No. of fibers 12
    Loose tube 1
    Sheath ø 7.6 mm
    Weight 68 kg/km
    Bending radius 115 mm
    Tensile load 1500 N
    Crush resistance 3000 N continuous
      5000 N short term
    Fire load 275 kWh/km
      990 MJ/km
    Length tolerances (prefabricated with plugs)
    Tolerances for lengths up to 40m ± 100 cm
    Tolerances for lengths up to 100m ± 100 cm
    Tolerances for lengths from 100m ± 2%
  • Optical properties

    Maximum attenuation (cabled)

    1310 nm: 0.34 / 1383 nm: 0.34* dB/km (*post hydrogen aging performance)

    Maximum Chromatic Dispersion

    3.5 ps/(nm x km)

    Zero Dispersion Wavelength λ0

    1304 ≤λ0≤ 1324 nm

    Maximim Zero Dispersion Slope So

    0.092 ps/(nm² x km)
    Mode-Filed Diameter 9.2 +/- 0,4 µm

    Maximum Cable Cut-off Wavelength λCC

    1260 nm
    PDM Link Design Value ≤ 0.04 ps/√km
    Max. individual fibre PMD ≤ 0.1 ps/√km
    Max. individual cable PMD ≤ 0.2 ps/√km
    Refractive Index 1.4676
    Mechanical properties
    Cladding diameter 125.0 +/- 1.0 µm
    Maximum Core/Cladding Concentricity Error 0.5 µm
    Maximum Cladding Non-Circularity 0.7 %
    Coating diameter

    245 +/-5 µm

    Maximum Cladding/Coating Concentricity Error 12 µm
    Operating temperature range -60 to +85°C
    Test load 100 kpsi
P/N Description Quantity
P-E2/E2-09B12Exxxx FO Universal Cable 12x E2000/12x E2000 12E9/125µ OS2 LSHF, Length: xxxx
P-E2/E2-09B24Exxxx FO Universal Cable 24x E2000/24x E2000 24E9/125µ OS2 LSHF, Length: xxxx
P-E2/E2-09B48Exxxx FO Universal Cable 48x E2000/48x E2000 48E9/125µ OS2 LSHF, Length: xxxx
P-E2/E2-09B72Exxxx FO Universal Cable 72x E2000/72x E2000 72E9/125µ OS2 LSHF, Length: xxxx
P-E2/E2-09B96Exxxx FO Universal Cable 96x E2000/96x E2000 96E9/125µ OS2 LSHF, Length: xxxx

back

Datasheet

Announcement texts